Information

This example compares the steam humidifier component to the steam humidifier models in the Fluid-package.


The results show good agreement with small differences that can be explained the following way.


The enthalpy of condensing gas in the medium model of the Fluid-package use the enthalpy of vaporization at 0 °C and the temperature difference to 0 °C multiplied with the specific heat capacity of steam.

The components in this package calculate the enthalpy difference of liquid water from 100 °C to the parameter TWatIn. Then the evaporation is calculated with the enthalpy of vaporization at 100 °C. Additional increase in temperature is possible using the specific heat capacity of steam.

Components

TypeNameDefaultDescription
Fluid.Sources.Boundary_pTsin
Fluid.Sources.MassFlowSource_Tsou
Fluid.Sensors.TemperatureTwoPortsenTem
Modelica.Blocks.Sources.RampramT
Modelica.Blocks.Sources.RampramXi
Modelica.Blocks.Sources.RampramMasFlo
Modelica.Blocks.Sources.ConstantTSet
Modelica.Blocks.Math.FeedbackresT
Modelica.Blocks.Sources.ConstantXSet
Modelica.Blocks.Math.FeedbackresX
Modelica.Blocks.Math.FeedbackresPow
Fluid.Sensors.MassFractionTwoPortsenMasFra
AixLib.Airflow.AirHandlingUnit.ModularAirHandlingUnit.Components.SteamHumidifiersteHum
Fluid.Humidifiers.GenericHumidifier_uhum
AixLib.Airflow.AirHandlingUnit.ModularAirHandlingUnit.Components.SteamHumidifiersteHum1
Fluid.Sources.MassFlowSource_Tsou1
Fluid.Humidifiers.SteamHumidifier_Xhum1
Fluid.Sensors.MassFractionTwoPortsenMasFra1
Fluid.Sensors.TemperatureTwoPortsenTem1
Fluid.Sources.Boundary_pTsin1
Modelica.Blocks.Math.FeedbackresT1
Modelica.Blocks.Math.FeedbackresX1
Modelica.Blocks.Math.FeedbackresPow1