modelBooleanExtractor

Validation model for the boolean extractor block

Information

Validation test for the block AixLib.Controls.OBC.CDL.Routing.BooleanExtractor.

The instances extIndBoo, extIndBoo1, extIndBoo2, extIndBoo3, and extIndBoo4 have the same input vector with dimension of 4. However, they have different extract index and thus different output.

  • The instance extIndBoo has the extract index of 2. The output is u[2].
  • The instance extIndBoo1 has the extract index of 6. Thus it is out of upper range [1, 4] and it outputs u[4]. It also issues a warning to indicate that the extract index is out of range.
  • The instance extIndBoo2 has the extract index of 0. Thus it is out of lower range [1, 4] and it outputs u[1]. It also issues a warning to indicate that the extract index is out of range.
  • The instance extIndBoo3 has the extract index changing from 2 to -1. Thus it first outputs u[2], and then changes to u[1]. At the moment when the extract index becomes out of range, it issues a warning.
  • The instance extIndBoo4 has the extract index changing from 0 to 3. Thus it first outputs u[1], and then changes to u[3]. It issues a warning at the start of the simulation.

Components

TypeNameDefaultDescription
AixLib.Controls.OBC.CDL.Routing.BooleanExtractorextIndBooExtracts signal from an input signal vector
AixLib.Controls.OBC.CDL.Routing.BooleanExtractorextIndBoo1Extracts signal from an input signal vector when the extract index is out of the upper range
AixLib.Controls.OBC.CDL.Routing.BooleanExtractorextIndBoo2Extracts signal from an input signal vector when the extract index is out of the lower range
AixLib.Controls.OBC.CDL.Routing.BooleanExtractorextIndBoo3Extracts signal from an input signal vector when the extract index changes from within range to out of range
AixLib.Controls.OBC.CDL.Routing.BooleanExtractorextIndBoo4Extracts signal from an input signal vector when the extract index changes from out of range to within range
AixLib.Controls.OBC.CDL.Logical.Sources.Constantcon1Block that outputs true signal
AixLib.Controls.OBC.CDL.Logical.Sources.ConstantconBlock that outputs false signal
AixLib.Controls.OBC.CDL.Logical.Sources.PulsebooPulGenerate pulse signal of type boolean
AixLib.Controls.OBC.CDL.Logical.Sources.PulsebooPul1Generate pulse signal of type boolean
AixLib.Controls.OBC.CDL.Integers.Sources.ConstantconIntIndex to extract input signal
AixLib.Controls.OBC.CDL.Integers.Sources.ConstantconInt1Index to extract input signal
AixLib.Controls.OBC.CDL.Integers.Sources.ConstantconInt2Index to extract input signal
AixLib.Controls.OBC.CDL.Integers.Sources.PulseintPulGenerate pulse signal of type Integer
AixLib.Controls.OBC.CDL.Integers.Sources.PulseintPul1Generate pulse signal of type Integer

Revisions

  • October 5, 2022, by Jianjun Hu:
    First implementation.