.AixLib.DataBase.CHP.CHPDataSimple.CHP_XRGI_9kWel

Information

Overview

EC Power mini-BHKW XRGI 9 (Natural Gas)

Concept

The electrical and thermal powers are in kW. The fuel input is in kW. The fuel consumption is in m³/h.

The calorific value of natural gas is assumed to be 11.5 kWh/m³ (10 - 12 kWh/m³).

Data Sheet (English, German)

"Data Sheet" cellspacing="0" cellpadding="0" border="0\

Max. noise level dB(A)

49

Dimensions (L x W x H) cm

92 x 64 x 96

Floor area m2

0.59

Weight kg</ p>

440

Service interval hours

10,000

Fuels: natural gas (all qualities), propane, butane

yes

Electrical output (modulating) kW

4 - 9

Thermal output kW

12 - 20

Power consumption (gas) kW

31

Electrical efficiency

29.5 %

Thermal efficiency excluding optional condenser

63.5 %

Total efficiency excluding optional condenser

93 %

Flow temperature (constant) °C

80 – 85

Max. return temperature (variable) °C

5 – 75

Maximum exhaust gas temperature °C

100

Emissions mg/Nm3

CO: < 50

NOX: < 100

Primary energy saving PES (EU Directive, verification in accordance with DIN 4709)

22.4 %

"Emmisions" cellspacing="0" cellpadding="0" border="0\

Emission

< ½ TA Luft

Primärenergieeinsparung PEE (EU-Richtlinie, Prüfung nach DIN 4709)

22,4 %

Primärenergiefaktor fp (EnEV 2009, EN15326)

0,53

Source:

Revisions


Generated at 2024-05-17T18:15:58Z by OpenModelicaOpenModelica 1.22.4 using GenerateDoc.mos