Measurement Data
cHQN:
0.00000e+00, 0.00000e+00, 3.25798e-07;
0.00000e+00, 2.73726e-05, 0.00000e+00;
-1.82165e-01, 0.00000e+00, 0.00000e+00
cPQN:
2.60353e-05, 1.85264e-03, -5.34076e-07, 5.03223e-10, -2.76211e-14;
0.00000e+00, 0.00000e+00, 1.18994e-06, 0.00000e+00, 0.00000e+00;
0.00000e+00, -8.47293e-05, 0.00000e+00, 0.00000e+00, 0.00000e+00;
-2.25479e-01, 0.00000e+00, 0.00000e+00, 0.00000e+00, 0.00000e+00
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Real | maxMinHeight (from PumpBaseRecord) | [-1, 16, 1; 0, 16, 1; 5, 12, 0.75; 10, 0.5, 0.5] | maximum and minimum boundaries of pump (Q [m3/h], Hmax [m], Hmin [m]) |
| Modelica.Units.NonSI.AngularVelocity_rpm | maxMinSpeedCurves (from PumpBaseRecord) | [-1, nMax, nMin; 0, nMax, nMin; 5, 0.5*nMax, nMin; 10, nMin, nMin] | maximum and minimum boundaries of pump speed (Q [m3/h], nMax [rev/min], nMin [rev/min]) |
| Modelica.Units.NonSI.AngularVelocity_rpm | nMin (from PumpBaseRecord) | 0 | minimum pump speed |
| Modelica.Units.NonSI.AngularVelocity_rpm | nMax (from PumpBaseRecord) | 0 | maximum pump speed |
| Real | cHQN (from PumpBaseRecord) | [0, 0, 0; 0, 0, 0; 0, 0, 0] | coefficients for H = f(Q,n) = sum_ij(cHQN[i,j] * Q^i * N^j) |
| Real | cPQN (from PumpBaseRecord) | [0, 0, 0; 0, 0, 0; 0, 0, 0] | coefficients for P = f(Q,H) = sum_ij(cPQN[i,j] * Q^i * N^j) Wilo coefficients: c4, c5, c6, c7, c8; 0, 0, c1, 0, 0; 0, c2, 0, 0, 0; c3, 0, 0, 0, 0 |
| Real | referenceDataQHPN (from PumpBaseRecord) | [0, 0, 0, 0, 0; 0, 0, 0, 0, 0; 0, 0, 0, 0, 0] | Table with measurement and calculated data for reference. 1. Q in m3/h, 2. H in m, 3. P in W, 4. N in rev/min (power limited pump speed), 5. N in rev/min (set point for pump speed) |