.AixLib.Electrical.Transmission.Functions.R_AC_correction

This function computes the correction factor of the DC resistance for AC systems at 60 Hz

Information

This function computes a correction factor for adapting the DC resistance when working with AC voltages. The correction factor assumes f = 60 Hz.

The correction is based on the type of cabel (AWG or kcmil) and the material.

Type (AWG or kcmil) Material Correction factor
1/0 Aluminium 1.0
2/0 Aluminium 1.001
3/0 Aluminium 1.001
4/0 Aluminium 1.001
250 Aluminium 1.002
300 Aluminium 1.003
350 Aluminium 1.004
400 Aluminium 1.005
500 Aluminium 1.007
600 Aluminium 1.010
700 Aluminium 1.013
750 Aluminium 1.015
800 Aluminium 1.017
1000 Aluminium 1.026
1250 Aluminium 1.040
1500 Aluminium 1.058
1750 Aluminium 1.079
2000 Aluminium 1.100
2500 Aluminium 1.142
Type (AWG or kcmil) Material Correction factor
1/0 Copper 1.0
2/0 Copper 1.001
3/0 Copper 1.002
4/0 Copper 1.004
250 Copper 1.005
300 Copper 1.006
350 Copper 1.009
400 Copper 1.011
500 Copper 1.018
600 Copper 1.025
700 Copper 1.034
750 Copper 1.039
800 Copper 1.044
1000 Copper 1.067
1250 Copper 1.102
1500 Copper 1.142
1750 Copper 1.185
2000 Copper 1.233
2500 Copper 1.326