.AixLib.Fluid.Actuators.BaseClasses.equalPercentage

Information

This function computes the opening characteristics of an equal percentage valve.

The function is used by the model AixLib.Fluid.Actuators.Valves.TwoWayEqualPercentage.

For y < delta/2, the valve characteristics is linear. For y > 3*delta/2 the valve characteristics is equal percentage. In between, a cubic spline is used to ensure that the valve characteristics is once continuously differentiable with respect to y.

Interface

function equalPercentage
  extends Modelica.Icons.Function;
  input Real y "Valve opening signal, y=1 is fully open";
  input Real R "Rangeability, R=50...100 typically";
  input Real l(min = 0, max = 1) "Valve leakage, l=Kv(y=0)/Kv(y=1)";
  input Real delta "Range of significant deviation from equal percentage law";
  output Real phi "Ratio actual to nominal mass flow rate, phi=Cv(y)/Cv(y=1)";
end equalPercentage;

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos