.AixLib.Fluid.Chillers.ModularReversible.RefrigerantCycle.TableData2D

Information

This model uses two-dimensional table data typically given by manufacturers as required by e.g. European Norm 14511 or ASHRAE 205 to calculate QEva_flow and PEle.

For different condenser outlet and evaporator inlet temperatures, the tables must provide two of the three following values: electrical power consumption, evaporator heat flow rate, and COP.

Note that losses are often implicitly included in measured data. In this case, the frosting modules should be disabled.

Scaling factor

For the scaling factor, the table data for evaporator heat flow rate (QEvaTabDat_flow) is evaluated at nominal conditions. Hence, the scaling factor is

scaFac = QEva_flow_nominal/QEvaTabDat_flow(TEva_nominal, TCon_nominal).

Using scaFac, the table data is scaled linearly. This implies a constant COP over different design sizes:

QEva_flow = scaFac * tabQEva_flow.y

PEle = scaFac * tabPel.y

Known Limitations

References

EN 14511-2018: Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors https://www.beuth.de/de/norm/din-en-14511-1/298537524