Compares the mass flow rate of the two pressure loss models HydraulicResistance and FixedResistanceDpM. For small pressure differences (up to 800 Pa) the flow rate of HydraulicResistance will be larger than the flow rate of FixedResistanceDpM. The difference is lower than 0.1 kg/s.
The parameters of the two models are chosen in a way to achieve the
same pressure drop. Results visualize the equation handling near
zero. Furthermore, the parameter HR.zeta
includes the
denominator 8 due to the calculation of final
dp_nominal=8*zeta*... in
the model HydraulicResistance.
Change parameter HR.from_dp
to false
and
the simulation time will increase by about 25 %.
Choosing this parameter depending whether you are using a mass flow source or a pressure source might improve the stability of the simulation.
Using a mass flow source and HR.from_dp = false
shows
similiar simulation speed as with HR.from_dp = true
.
Name | Description |
---|---|
Medium |