This model contains a calculation procedure for engine efficiency models (for more information, please check out AixLib.Fluid.Movers.Compressors.BaseClasses.PartialCompression). The calculation procedures based on a power approach are presented below.
Actually, one power approache is implemented in this package. To
add further calculation procedures, just add its name in AixLib.Fluid.Movers.Compressors.Utilities.Types
and expand the if-structure.
| Reference | Formula | Refrigerants | Validity ncompressor |
Validity Πpressure |
|---|---|---|---|---|
| MendozaMirandaEtAl2016 | ηeng = a1 * π^b1 * (nref/n)^b2 *
(1/((TInl+TOutIse)/2-TOut))^b3 *
(Mref/M)^b4 |
R134a,R450a,R1324yf,R1234ze(E) | 0 - 50 |
1 - 6 |
J.M. Mendoza-Miranda, A. Mota-Babiloni, J.J. Ramírez-Minguela, V.D. Muñoz-Carpio, M. Carrera-Rodríguez, J. Navarro-Esbrí and C. Salazar-Hernández (2016): Comparative evaluation of R1234yf, R1234ze(E) and R450A as alternatives to R134a in a variable speed reciprocating compressor. In: Energy 114, S. 753–766