.AixLib.Fluid.Movers.Compressors.Utilities.VolumetricEfficiency.PowerVolumetricEfficiency

Information

This model contains a calculation procedure for volumetric efficiency models (for more information, please check out AixLib.Fluid.Movers.Compressors.BaseClasses.PartialCompression). The calculation procedures based on a power approach are presented below.

Implemented approaches

Actually, one power approache is implemented in this package. To add further calculation procedures, just add its name in AixLib.Fluid.Movers.Compressors.Utilities.Types and expand the if-structure.

"Power approaches" border="1" cellspacing="0" cellpadding="2" style="border-collapse:collapse;">
Reference Formula Refrigerants Validity ncompressor Validity Πpressure
MendozaMirandaEtAl2016 ηvol = a1 * π^b1 * (π^1.5*n^3*Vdis)^b2 * (Mref/M)^b3 R134a,R450a,R1324yf,R1234ze(E) 0 - 50 1 - 6

References

J.M. Mendoza-Miranda, A. Mota-Babiloni, J.J. Ramírez-Minguela, V.D. Muñoz-Carpio, M. Carrera-Rodríguez, J. Navarro-Esbrí and C. Salazar-Hernández (2016): Comparative evaluation of R1234yf, R1234ze(E) and R450A as alternatives to R134a in a variable speed reciprocating compressor. In: Energy 114, S. 753–766