This component calculates the solar radiation necessary for the fluid in the collector to gain heat. It is used in the model AixLib.Fluid.SolarCollectors.Controls.CollectorPump.

The critical solar radiation level is calculated using Equation 6.8.2 in Duffie and Beckman (2006). It is

GTC=FRUL (TIn-TEnv) /(FR(τα))

where GTC is the critical solar radiation, FRUL is the heat loss coefficient, TIn is the inlet temperature, TEnv is the ambient temperature, and FR(τα) is the maximum efficiency.

References

J.A. Duffie and W.A. Beckman 2006, Solar Engineering of Thermal Processes (3rd Edition), John Wiley & Sons, Inc.