modelSafetyControl
Information
Stops the boiler if the flow temperature exceeds the maxmium flow temperature.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.Temperature | TFlowMax | 378.15 | Maximum flow temperature, at which the system is shut down |
| Modelica.Units.SI.Temperature | TRetMin | 313.15 | Minimum return temperature, at which the system is shut down |
| Modelica.Units.SI.Time | time_minOff | 900 | Time after which the device can be turned on again |
| Modelica.Units.SI.Time | time_minOn | 900 | Time after which the device can be turned off again |
Connectors
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Interfaces.RealInput | TSupMea | Measured flow temperature of boiler | |
| Modelica.Blocks.Interfaces.BooleanOutput | isOn | Set value for on/off status of boiler after emergency check | |
| Modelica.Blocks.Interfaces.BooleanInput | isOnSet | Set value for on off status of boiler | |
| Modelica.Blocks.Interfaces.RealInput | TRetMea | Measured return temperature of boiler |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Blocks.Sources.RealExpression | TSupMaxExp | Real expression for maximum expected flow temperature | |
| Modelica.Blocks.Logical.Greater | greater | ||
| DeviceStatusDelay | devStaDel |
Revisions
-
June, 2023 by Moritz Zuschlag; David Jansen
First Implementation (see issue #1147)