modelCtrTabs
Controller for concrete core activation
Information
Simple controller for TABS. The temperature of the water that flows
into the concrete is controlled.
Parameters
| Type | Name | Default | Description |
| Boolean | useExternalTset | false | If True, set temperature can be given externally |
| Modelica.Units.SI.Temperature | TflowSet | 293.15 | Flow temperature set point of consumer |
| Real | offset | 0.1 | Constant offset between cooling and heating setpoint to avoid oscillations and simultaneous cooling and heating. |
| Hot water supply circuit |
| Real | k_hot | 0.03 | Gain of controller for the hot throttle circuit |
| Modelica.Units.SI.Time | Ti_hot | 60 | Time constant of Integrator block for the hot throttle circuit |
| Real | rpm_pump_hot | 3000 | Rpm of the pump of the hot throttle circuit |
| Cold water supply circuit |
| Real | k_cold | 0.03 | Gain of controller for the cold throttle circuit |
| Modelica.Units.SI.Time | Ti_cold | 60 | Time constant of Integrator block the cold throttle circuit |
| Real | rpm_pump_cold | 3000 | Rpm of the pump of the cold throttle circuit |
| Concrete supply circuit |
| Modelica.Units.NonSI.AngularVelocity_rpm | rpm_pump_concrete | 2500 | Rpm of the Pump that supplies the concrete core |
Revisions
- December 09, 2021, by Alexander Kümpel:
First implementation.