The package
AixLib.ThermalZones.HighOrder.Validation.ASHRAE140
consists of models for several comparative test cases according to
the standard ASHRAE140.
All implemented comparative test cases refer to changes to the input
specifications for Building Thermal Envelope and Fabric Load
Tests.
The standard ASHRAE140 provides detailed descriptions of all test
cases.
Case600 represents the base-building model, which is the basis for
all following cases.
The base-building is a single-story, low-mass building with
rectangular geometry, 48 m2 floor area and 12 m2 of south-facing
windows.
Case number |
Low Mass / High Mass |
Window Orientation |
Air Exchange Rate [ach] |
Thermostat Control |
Internal Gains [W] |
Solar Absorptance | Infrared Emittance |
---|---|---|---|---|---|---|---|
600 | Low Mass | South | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp > 7°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.6 interior: 0.6 |
The following table describes the input specifications for all Building Thermal Envelope and Fabric Load Test Cases.
Case number |
Low Mass / High Mass |
Window Orientation |
Air Exchange Rate [ach] |
Thermostat Control |
Internal Gains [W] |
Solar Absorptance | Infrared Emittance |
---|---|---|---|---|---|---|---|
600 | Low Mass | South | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp > 7°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
620 | Low Mass | East/West | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp > 7°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
640 | Low Mass | South | 0.41 |
23-7 h: Heat = ON IF Temp < 10°C 7-23 h: Heat = ON IF Temp < 20°C; Cool = ON IF Temp > 27°C |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
650 | Low Mass | South | 10.8 |
18-7 h: Vent fan = ON 7-18 h: Vent fan = OFF Heating = always OFF 18-7 h:Cool = OFF 7-18 h: Cool =ON IF Temp>27°C |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
900 | High Mass | South | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp > 7°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
920 | High Mass | East/West | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp > 7°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
940 | High Mass | South | 0.41 |
23-7 h: Heat = ON IF Temp < 10°C 7-23 h: Heat = ON IF Temp < 20°C; Cool = ON IF Temp > 27°C |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
950 | High Mass | South | 10.8 |
18-7 h: Vent fan = ON 7-18 h: Vent fan = OFF Heating = always OFF 18-7 h:Cool = OFF 7-18 h: Cool =ON IF Temp > 27°C |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
220 | Low Mass | South (opak) | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
210 | Low Mass | South (opak) | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.1 |
230 | Low Mass | South (opak) | 0.822 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
240 | Low Mass | South (opak) | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
200 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
250 | Low Mass | South (opak) | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.9 interior: - |
exterior: 0.9 interior: 0.9 |
270 | Low Mass | South | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: 0.9 |
exterior: 0.9 interior: 0.9 |
280 | Low Mass | South | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: 0.1 |
exterior: 0.9 interior: 0.9 |
300 | Low Mass | East/West | 0 |
Heat = ON IF Temp < 20°C Cool ON IF Temp > 20°C |
0 |
exterior: 0.1 interior: 0.9 |
exterior: 0.9 interior: 0.9 |
320 | Low Mass | South | 0 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
0 |
exterior: 0.1 interior: 0.9 |
exterior: 0.9 interior: 0.9 |
400 | Low Mass | South (opak) | 0 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
395 | Low Mass | no window | 0 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
410 | Low Mass | South (opak) | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
0 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
420 | Low Mass | South (opak) | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
200 |
exterior: 0.1 interior: - |
exterior: 0.9 interior: 0.9 |
430 | Low Mass | South (opak) | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: - |
exterior: 0.9 interior: 0.9 |
440 | Low Mass | South | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.1 |
exterior: 0.9 interior: 0.9 |
800 | High Mass | South (opak) | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: - |
exterior: 0.9 interior: 0.9 |
810 | High Mass | South | 0.41 |
Heat = ON IF Temp < 20°C; otherwise Heat=OFF Cool = ON IF Temp < 27°C; otherwise Cool = OFF |
200 |
exterior: 0.6 interior: 0.1 |
exterior: 0.9 interior: 0.9 |
The following FreeFloating models refer to test cases that do not include mechanical heating or cooling of the building.
Case number |
Low Mass / High Mass |
Window Orientation |
Air Exchange Rate [ach] |
Thermostat Control |
Internal Gains [W] |
Solar Absorptance | Infrared Emittance |
---|---|---|---|---|---|---|---|
600FF | Low Mass | South | 0.41 | No mechanichal heating or cooling | 200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
650FF | Low Mass | South | 0.41 |
No mechanical heating/cooling but vent fan : 18-7 Uhr Vent fan = ON 7-18 Uhr Vent fan = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
900FF | High Mass | South | 0.41 | No mechanichal heating or cooling | 200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
950FF | High Mass | South | 0.41 |
No mechanical heating/cooling but vent fan : 18-7 Uhr Vent fan = ON 7-18 Uhr Vent fan = OFF |
200 |
exterior: 0.6 interior: 0.6 |
exterior: 0.9 interior: 0.9 |
The simulated annual heating and cooling loads of Case
210, 250, 395, 430 cannot meet the statistical
acceptance ranges given by ASHRAE140 (01.01.2021).
However, cases that do not perform according to the
reference values should not be considered erroneous. They
shall be used as indication for debugging purposes
instead.