Overview
Building 1 is part of an empirical validation according to an
internal monitoring study with permission to use data anonymized.
Specifications are:
- length = 72 m
- heigth = 22 m
- width = 22 m
- no windows, except for 60m² window area on the ceiling (smoke
ventilation windows)
Air exchange rates:
- n50 = 0.1 1/h, due to air leakage
- n = 1 1/h, due to air exchange caused by open ventilation windows
(opening schedule in Building specifications{5})
- n = 0.25 1/h, due to air exchange caused by open door to room
next to building 1 (schedule 7 am - 4 pm)
Building specifications give information about:
- {2} measured room temperatur in the building: temperature sensor
at the top
- {3} measured room temperatur in the building: temperature sensor
at the center
- {4} measured room temperatur in the building: temperature sensor
at the bottom
- {5} air exchange due to windows (smoke ventilation windows) in
the ceiling
Assumptions:
- 30 % of the volume is constantly filled with goods and
shelves
- Internal capacity: 2100000 kg, specific heat capacity: 2000 J/kg