VDI 6007 Test Case 7 model
Test Case 7 of the VDI 6007 Part 1: Calculation of heat load
excited with a given radiative heat source and a setpoint profile
for room version S. Is similar with Test Case 6, but with a maximum
heating/cooling power.
Boundary conditions
- constant outdoor air temperature 22°C
- no solar or short-wave radiation on the exterior wall
- no solar or short-wave radiation through the windows
- no long-wave radiation exchange between exterior wall, windows
and ambient environment
This test validates heat load calculation with maximum heating
power.
- July 11, 2019, by Katharina Brinkmann:
Renamed alphaWall to hConWall
- January 25, 2019, by Michael Wetter:
Added start value to avoid warning in JModelica.
- July 7, 2016, by Moritz Lauster:
Added automatic check against validation thresholds.
- January 11, 2016, by Moritz Lauster:
Implemented.