This block computes the wet bulb temperature for a given dry bulb temperature, relative air humidity and atmospheric pressure.
If the constant approximateWetBulb is true,
then the block uses the approximation of Stull (2011) to compute
the wet bulb temperature without requiring a nonlinear equation.
Otherwise, the model will introduce one nonlinear equation.
The approximation by Stull is valid for a relative humidity of 5% to 99%,
a temperature range from -20°C to 50°C
and standard sea level pressure.
For this range of data, the approximation error is -1 Kelvin to +0.65 Kelvin,
with a mean error of less than 0.3 Kelvin.
Otherwise a calculation based on an energy balance is used. See #474 for a discussion. The model is validated in AixLib.Utilities.Psychrometrics.Examples.TWetBul_TDryBulPhi.
For a model that takes the mass fraction instead of the relative humidity as an input, see AixLib.Utilities.Psychrometrics.TWetBul_TDryBulXi.
Stull, Roland. Wet-Bulb Temperature from Relative Humidity and Air Temperature Roland Stull. Journal of Applied Meteorology and Climatology. Volume 50, Issue 11, pp. 2267-2269. November 2011 DOI: 10.1175/JAMC-D-11-0143.1