Validation test for the block
Buildings.Air.Systems.SingleZone.VAV.BaseClasses.ControllerEconomizer.
The inputs include:
-
Mixed air temperature
mixAirTem
, varying from 12.5 °C
to 27.5 °C
-
Return air temperature
retAirTem
, varying from 17.0 °C
to 25.0 °C
-
Mixed air temperature setpoint
mixAirTemSet
, varying from 15.0
°C to 25.0 °C
-
Outdoor air temperature
outAirTem
, varying from 12.0
°C to 24.0 °C
-
Minimum outdoor air fraction
minOutAirFra
, varying from 0.05
to 0.35
-
Cooling status signal
cooSta
, set to true.
-
July 28, 2020, by Kun Zhang:
Added cooling status input signal and removed obsoleted heating control signal.
-
July 3, 2017, by Jianjun Hu:
First implementation.