Chilled water plant with a non-integrated waterside economizer (WSE) have two cooling modes: free cooling (FC) mode and fully mechanical cooling (FMC) mode. This model determines when to activate FC or FMC for a chilled water system with 2 chillers and 1 waterside economizer.
The FMC mode is activated when
and the FC mode is activated when
where TWetBulb is the wet bulb temperature of the outdoor air, TWetBulb,tran is the wet bulb temperature transition point for switching between FC and FMC, TCHWST is the chilled water supply temperature, TCHWSTSet is the chilled water supply temperature setpoint,and numOnChi is the number of running chillers.