This is a partial model that describes the chilled water cooling system in a data center. The sizing data
are collected from the reference.
Reference
-
Taylor, S. T. (2014). How to design & control waterside economizers. ASHRAE Journal, 56(6), 30-36.
Contents
-
January 2, 2022, by Kathryn Hinkelman:
Passed the plaOn
signal to the chilled water pump control
to turn them off when the plant is off.
-
November 16, 2022, by Michael Wetter:
Corrected control to avoid cooling tower pumps to operate when plant is off, because
shut-off valves are off when plant is off.
-
November 1, 2021, by Michael Wetter:
Corrected weather data bus connection which was structurally incorrect
and did not parse in OpenModelica.
This is for
issue 2706.
-
October 6, 2020, by Michael Wetter:
Set val.use_inputFilter=false
because pump worked against closed valve at t=60 seconds,
leading to negative pressure at pump inlet (because pump forces the mass flow rate).
-
January 12, 2019, by Michael Wetter:
Removed wrong each
.
-
December 1, 2017, by Yangyang Fu:
Used scaled differential pressure to control the speed of pumps. This can avoid retuning gains
in PID when changing the differential pressure setpoint.
-
September 2, 2017, by Michael Wetter:
Changed expansion vessel to use the more efficient implementation.
-
July 30, 2017, by Yangyang Fu:
First implementation.
Generated at 2024-11-22T19:25:38Z
by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos