Multi zone VAV AHU economizer control sequence that calculates
outdoor and return air damper positions based on ASHRAE
Guidline 36, May 2020, Sections: 5.16.2.3,5.16.4, 5.16.5, 5.16.6, 5.16.7.
The sequence consists of three sets of subsequences.
-
March 1, 2023, by Michael Wetter:
Changed constants from 0
to 0.0
and 1
to 1.0
.
This is for
#3267.
-
August 1, 2020, by Jianjun Hu:
Updated implementation according to ASHRAE G36 official release.
-
October 11, 2017, by Michael Wetter:
Corrected implementation to use control loop signal as input.
-
June 28, 2017, by Milica Grahovac:
First implementation.