Block that outputs the position limits of the return and outdoor air damper for units with a separated minimum outdoor air damper and airflow measurement. It is implemented according to Section 5.16.5 of the ASHRAE Guideline 36, May 2020.
Calculate the outdoor air set point with Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.
Minimum outdoor air control loop is enabled when the supply fan is proven ON
(u1SupFan=true
) and in occupied mode, and disabled and output set to
zero otherwise
The minimum outdoor airflow rate shall be maintained at the minimum outdoor air
set point by a reverse-acting control loop whose output is 0% to 100%.
From 0% to 50% loop output, the minimum outdoor air damper is opened from 0%
(minOutDamPhy_min
) to 100% (minOutDamPhy_max
).
retDamPhy_max
) to 0% (retDamPhy_min
)
as the minimum outdoor air loop output rises from 50% to 100%.