.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithAFMS

Information

Block that outputs the position limits of the return and outdoor air damper for units with a separated minimum outdoor air damper and airflow measurement. It is implemented according to Section 5.16.5 of the ASHRAE Guideline 36, May 2020.

Minimum outdoor air set point

Calculate the outdoor air set point with Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.

Minimum outdoor air control loop

Minimum outdoor air control loop is enabled when the supply fan is proven ON (u1SupFan=true) and in occupied mode, and disabled and output set to zero otherwise

The minimum outdoor airflow rate shall be maintained at the minimum outdoor air set point by a reverse-acting control loop whose output is 0% to 100%. From 0% to 50% loop output, the minimum outdoor air damper is opened from 0% (minOutDamPhy_min) to 100% (minOutDamPhy_max).

Return air damper

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos