.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Limits.SeparateWithDP

Information

Block that outputs the position limits of the return and outdoor air damper for units with a separated minimum outdoor air damper and differential pressure control. It is implemented according to Section 5.16.4 of the ASHRAE Guideline 36, May 2020.

Differential pressure setpoint across the minimum outdoor air damper

Open minimum outdoor air damper

Open minimum outdoor air damper when the supply air fan is proven ON and the system is in occupied mode and the minimum differential pressure set point is greater than zero. Damper shall be closed otherwise.

Return air damper