Block that outputs the position limits of the return and outdoor air damper for units
with a separated minimum outdoor air damper and differential pressure control.
It is implemented according to Section 5.16.4 of the ASHRAE Guideline 36, May 2020.
Differential pressure setpoint across the minimum outdoor air damper
Open minimum outdoor air damper
Open minimum outdoor air damper when the supply air fan is proven ON and the system
is in occupied mode and the minimum differential pressure set point is greater
than zero. Damper shall be closed otherwise.
Return air damper
-
Return air damper minimum outdoor air control is enabled when the minimum outdoor
air damper is open and the economizer outdoor air damper is less than a projected
position limit, which is 5% when supply fan speed is at 100% design speed proportionally
up to 80% when the fan is at minimum speed.
-
Return air damper minimum outdoor air control is disabled when the minimum outdoor
air damper is closed or the economizer outdoor air damper is 10% above the projected
position limit as determined above.
-
When enabled, the maximum return air damper set point is modulated from 100% to 0%
to maintain the differential pressure across the minimum outdoor air damper at set
point.
-
August 29, 2023, by Hongxiang Fu:
Because of the removal of Logical.And3
based on ASHRAE 231P,
replaced it with a stack of two Logical.And
blocks.
This is for
#2465.
-
August 1, 2020, by Jianjun Hu:
First implementation.