.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.AHU

Information

This sequence outputs AHU level effective outdoor air absolute minimum and design minimum setpoints VEffAbsOutAir_flow, VEffDesOutAir_flow and the nomalized minimum setpoint effOutAir_normalized when complying with California Title 24 ventilation requirements. It is implemented according to Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.

It calculates as below:

  1. See the sum of zone absolute and design minimum outdoor airflow setpoint VSumZonAbsMin_flow and VSumZonDesMin_flow from Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone for the detailed description.
  2. Effective outdoor air absolute minimum and design minimum setpoints (VEffAbsOutAir_flow and VEffDesOutAir_flow) are recalculated continuously based on the mode of the zones being served.
  3. According to section 5.16.4, 5.16.5 and 5.16.6, the effective minimum outdoor airflow setpoint should be reset based on the highest zone CO2 control- loop signal from VEffAbsOutAir_flow at 50% signal to VEffDesOutAir_flow at 100% signal. When there is no CO2 sensor in any zone, the effective minimum outdoor airflow setpoint should be equal to the VEffDesOutAir_flow.

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos