This sequence outputs AHU level effective outdoor air absolute minimum and design
minimum setpoints VEffAbsOutAir_flow, VEffDesOutAir_flow and
the nomalized minimum setpoint effOutAir_normalized
when complying with California Title 24 ventilation requirements.
It is implemented according to Section 5.16.3.2 of ASHRAE
Guideline G36, May 2020.
It calculates as below:
VSumZonAbsMin_flow and VSumZonDesMin_flow from
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.Title24.SumZone for the detailed
description.
VEffAbsOutAir_flow and VEffDesOutAir_flow) are recalculated
continuously based on the mode of the zones being served.
VEffAbsOutAir_flow is
the sum of VZonAbsMin_flow for all zones in all zone groups that
are in occupied mode but shall be no larger than the absolute minimum outdoor airflow
VAbsOutAir_flow.
VEffDesOutAir_flow is
the sum of VZonDesMin_flow for all zones in all zone groups that
are in occupied mode but shall be no larger than the absolute minimum outdoor airflow
VDesOutAir_flow.
VEffAbsOutAir_flow at 50% signal to VEffDesOutAir_flow
at 100% signal. When there is no CO2 sensor in any zone, the effective minimum
outdoor airflow setpoint should be equal to the VEffDesOutAir_flow.