Sequence for controlling actuated relief damper yRelDam
for AHUs using
actuated relief damper without a fan.
It is implemented according to Section 5.16.8 of ASHRAE Guideline G36, May 2020.
-
Relief dampers shall be enabled when the associated supply fan is proven on
(
u1SupFan = true
), and disabled otherwise.
-
When enabled, use a P-only control loop to modulate relief dampers to maintain building
static pressure
dpBui
at its setpoint, which is by defaul
12 Pa (0.05 inchWC).
-
Close damper when disabled.
-