.Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.SupplyFan

Information

Supply fan control for a multi zone VAV AHU according to Section 5.16.1 of ASHRAE Guideline G36, May 2020.

Supply fan start/stop

Static pressure setpoint reset

Static pressure setpoint shall be reset using trim-respond logic using following parameters as a starting point:

Variable Value Definition
DeviceAHU Supply Fan Associated device
SP0iniSetInitial setpoint
SPminminSetMinimum setpoint
SPmaxmaxSetMaximum setpoint
TddelTimDelay timer
TsamplePeriodTime step
InumIgnReqNumber of ignored requests
RuZonPreResReqNumber of requests
SPtrimtriAmoTrim amount
SPresresAmoRespond amount
SPres_maxmaxResMaximum response per time interval

Static pressure control

Supply fan speed is controlled with a PI controller to maintain duct static pressure at setpoint when the fan is proven on. The setpoint for the PI controller and the measured duct static pressure are normalized with the maximum design static presssure maxSet. Where the zone groups served by the system are small, provide multiple sets of gains that are used in the control loop as a function of a load indicator (such as supply fan airflow rate, the area of the zone groups that are occupied, etc.).