modelReturnFanDirectPressure

Validate model for calculating return fan control with direct building pressure of multi zone VAV AHU

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.ReturnFanDirectPressure for exhaust air damper and return fan control with direct building pressure measurement for systems with multiple zones.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.ReturnFanDirectPressureretFanPreReturn fan control with direct building pressure
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.ReturnFanDirectPressureretFanPre1Return fan control with direct building pressure
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.ReturnFanDirectPressureretFanPre2Return fan control with direct building pressure
Buildings.Controls.OBC.CDL.Logical.Sources.PulseyFanSupply fan status
Buildings.Controls.OBC.CDL.Reals.Sources.RampdpBuiBuilding static presure

Revisions

  • October 16, 2017, by Michael Wetter:
    Changed example to also test for fan off signal.
  • October 16, 2017, by Jianjun Hu:
    First implementation.