.Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Economizers.Validation.Controller_Mod_DamLim

Validation model for single zone VAV AHU economizer operation: damper modulation and minimum ooutdoor air requirement damper position limits

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Economizers.Controller control loops: minimum outdoor air damper position limits control loop (economizer block) and modulation control loop (economizer1 block) for VOut_flow and TSup control signals. Both control loops are enabled during the validation test.