Sequence for controlling actuated relief damper yRelDam
for AHUs using
actuated relief damper without a fan.
It is implemented according to Section 5.18.8 of ASHRAE Guideline G36, May 2020.
In Section 3.2.2.3, find the relief damper position setpoint limits:
relDam_min
: the relief damper position that maintainx a building pressure
of 12 Pa (0.05 in. of water) while the economizer is positioned to provide minimum
outdoor airflow while the supply fan is at minimum speed.
relDam_max
: the relief damper position that maintainx a building pressure
of 12 Pa (0.05 in. of water) while the economizer damper is fully open and the fan
speed is at cooling maximum.
Relief damper shall be enabled when the associated supply fan is proven on and any outdoor air damper is open, and disabled and closed otherwise.
Relief damper position shall be reset lineary from relDam_min
to
relDam_max
as the commanded economizer damper position goes from
uOutDam_min
to 100% open.