.Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.ReliefDamper

Information

Sequence for controlling actuated relief damper yRelDam for AHUs using actuated relief damper without a fan. It is implemented according to Section 5.18.8 of ASHRAE Guideline G36, May 2020.

In Section 3.2.2.3, find the relief damper position setpoint limits:

Relief damper shall be enabled when the associated supply fan is proven on and any outdoor air damper is open, and disabled and closed otherwise.

Relief damper position shall be reset lineary from relDam_min to relDam_max as the commanded economizer damper position goes from uOutDam_min to 100% open.

Image of the relief damper control chart for single zone AHU