Sequence for controlling return fan yRetFan
for single AHUs.
It is implemented according to Section 5.18.10 of ASHRAE Guideline G36, May 2020.
-
Exhaust damper shall open whenever associated supply fan is proven on.
-
Return fan shall run whenever associated supply fan is proven on.
-
Return fan speed shall be the same as supply fan speed with a user adjustable offset.
See Section 3.2.1.5 for details about the offset.
-
Exhaust damper shall be closed when return fan is disabled.
-