modelFreezeProtection_Disable

Validate model for disabling freeze protection

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.FreezeProtection for air handling unit serving single zones, when disabling the freeze protection.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.FreezeProtectionfreProFreeze protection control
Buildings.Controls.OBC.CDL.Reals.Sources.RampoutDamPosOutdoor air damper position
Buildings.Controls.OBC.CDL.Reals.Sources.RampheaCoiPosHeating coil position
Buildings.Controls.OBC.CDL.Reals.Sources.RampretDamPosReturn air damper position
Buildings.Controls.OBC.CDL.Reals.Sources.RampsupFanSpeSupply fan speed
Buildings.Controls.OBC.CDL.Reals.Sources.RampcooCoiPosCooling coil position
Buildings.Controls.OBC.CDL.Reals.GreaterThresholdgreThrCheck if the supply fan is proven on

Revisions

  • December 22, 2022, by Jianjun Hu:
    First implementation.