modelController

Validation of the top-level controller

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Controller.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.ControllerconVAVValidate the cooling case
Buildings.Controls.OBC.CDL.Reals.Sources.RampTZonMeasured zone temperature
Buildings.Controls.SetPoints.OccupancyScheduleoccSchOccupancy schedule
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTOutOutdoor air dry bulb temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantcooDowTimCooling down time
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantwarUpTimWarm-up time
Buildings.Controls.OBC.CDL.Reals.Sources.SincooSetAdjCooling setpoint adjustment
Buildings.Controls.OBC.CDL.Reals.Sources.SinheaSetAdjHeating setpoint adjustment
Buildings.Controls.OBC.CDL.Logical.Sources.PulsewinStaGenerate signal indicating window status
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantzerAdjZero adjustment
Buildings.Controls.OBC.CDL.Reals.Switchswi1Switch to zero adjustment when window is open
Buildings.Controls.OBC.CDL.Reals.Switchswi2Switch to zero adjustment when window is open
Buildings.Controls.OBC.CDL.Logical.Sources.PulseoccStaGenerate signal indicating occupancy status
Buildings.Controls.OBC.CDL.Integers.Sources.ConstantdemLimLevDemand limit level
Buildings.Controls.OBC.CDL.Logical.Sources.PulsefreResFreeze protection reset
Buildings.Controls.OBC.CDL.Logical.Notnot1Logical not
Buildings.Controls.OBC.CDL.Reals.Sources.RampmixTemMixed air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.RampoutDamOutdoor damper position
Buildings.Controls.OBC.CDL.Reals.Sources.RampcooCoiCooling coil position
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantheaCoiHeating coil position
Buildings.Controls.OBC.CDL.Reals.Sources.RampTSupTerminal unit discharge air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTHeaSetOccOccupied heating setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTCooSetOccOccupied cooling setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTHeaSetUnoUnoccupied heating setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTCooSetUnoUnoccupied cooling setpoint
CDL.Logical.Notnot2Logical not

Revisions

  • February 9, 2022, by Jianjun Hu:
    First implementation.