Controller for cooling only terminal box according to Section 5.5 of ASHRAE
Guideline 36, May 2020. It outputs discharge airflow setpoint VSet_flow
,
damper position setpoint yDam
, AHU cooling supply temperature
setpoint reset request yZonTemResReq
, and static pressure setpoint
reset request yZonPreResReq
. It also outputs the alarms about the low airflow
yLowFloAla
, leaking damper yLeaDamAla
, and
airflow sensor calibration alarm yFloSenAla
.
The sequence consists of six subsequences.
The subsequence is implementd according to Section 5.3.4. The measured zone
temperature TZon
, zone setpoints temperatures TZonHeaSet
and
TZonCooSet
are inputs to the instance of class
Buildings.Controls.OBC.ASHRAE.G36.ThermalZones.ZoneStates to generate the
heating and cooling control loop signal.
This sequence sets the active maximum and minimum airflow according to
Section 5.5.4. Depending on operation modes uOpeMod
, it sets the
airflow rate limits for cooling supply.
See
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.ActiveAirFlow.
This sequence sets the damper position setpoints for the terminal unit. The implementation is according to Section 5.5.5. According to heating and cooling control loop signal, along with the active maximum and minimum airflow setpoint, measured zone temperature, the sequence outputs damper position setpoint, and active airflow rate setpoint. See Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Dampers.
According to Section 5.5.8, this sequence outputs the system reset requests, i.e.
cooling supply air temperature reset requests yZonTemResReq
,
static pressure reset requests yZonPreResReq
.
See
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.SystemRequests.
According to Section 5.5.6, this sequence outputs the alarms of low discharge flow, leaking damper and airflow sensor calibration alarm. See Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Alarms.
According to Section 5.5.7, this sequence allows the override the aiflow setpoints, damper position setpoints. See Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Dampers.
have_preIndDam
to exclude the option of using pressure independant damper.