This block outputs alarms of cooling only terminal unit. The implementation is according to the Section 5.5.6 of ASHRAE Guideline 36, May 2020.
staTim, if the measured airflow
VDis_flow is less than 70% of setpoint
VActSet_flow for 5 minutes (lowFloTim)
while the setpoint is greater than zero, generate a Level 3
alarm.staTim, if the measured airflow
VDis_flow is less than 50% of setpoint
VActSet_flow for 5 minutes (lowFloTim)
while the setpoint is greater than zero, generate a Level 2
alarm.staPreMul)
of 0 for its static pressure reset Trim-Respond control loop, low
airflow alarms shall be suppressed for that zone.If the fan serving the zone has been OFF
(uFan=false) for 10 minutes (fanOffTim),
and airflow sensor reading VDis_flow is above 10% of
the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
If the damper position (uDam) is 0% and airflow
sensor reading VDis_flow is above 10% of the cooling
maximum airflow setpoint VCooMax_flow for 10 minutes
(leaFloTim) while the fan serving the zone is proven
on (uFan=true), generate a Level 4 alarm.
Logical.And3 based on ASHRAE
231P, replaced it with a stack of two Logical.And
blocks. This is for #2465.staTim to allow the system becoming
stabilized. This is for issue
3257.