This sequence outputs the system reset requests for cooling only terminal unit. The implementation is according to the Section 5.5.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReq
TZon
exceeds the zone cooling setpoint
TZonCooSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSup=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonTemResReq=3
).
TZon
exceeds the zone cooling setpoint
TZonCooSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSup=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonTemResReq=2
).
uCoo
is greater than 95%, send 1 request
(yZonTemResReq=1
) until uCoo
is less than 85%.
uCoo
is less than 95%, send 0 request (yZonTemResReq=0
).
yZonPreResReq
VDis_flow
is less than 50% of setpoint
VSet_flow
while the setpoint is greater than zero and the damper position
uDam
is greater than 95% for 1 minute, send 3 requests (yZonPreResReq=3
).
VDis_flow
is less than 70% of setpoint
VSet_flow
while the setpoint is greater than zero and the damper position
uDam
is greater than 95% for 1 minute, send 2 requests (yZonPreResReq=2
).
uDam
is greater than 95%, send 1 request
(yZonPreResReq=1
) until uDam
is less than 85%.
uDam
is less than 95%, send 0 request
(yZonPreResReq=0
).