This sequence outputs the system reset requests for cooling only terminal unit. The implementation is according to the Section 5.5.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReqTZon exceeds the zone
cooling setpoint TZonCooSet by 3 °C (5 °F)) for 2
minutes and after suppression period (uAftSup=true)
due to setpoint change per G36 Part 5.1.20, send 3 requests
(yZonTemResReq=3).TZon exceeds the zone
cooling setpoint TZonCooSet by 2 °C (3 °F) for 2
minutes and after suppression period (uAftSup=true)
due to setpoint change per G36 Part 5.1.20, send 2 requests
(yZonTemResReq=2).uCoo is greater than 95%,
send 1 request (yZonTemResReq=1) until
uCoo is less than 85%.uCoo is less than 95%, send 0 request
(yZonTemResReq=0).yZonPreResReqVDis_flow is less than 50%
of setpoint VSet_flow while the setpoint is greater
than zero and the damper position uDam is greater than
95% for 1 minute, send 3 requests
(yZonPreResReq=3).VDis_flow is less
than 70% of setpoint VSet_flow while the setpoint is
greater than zero and the damper position uDam is
greater than 95% for 1 minute, send 2 requests
(yZonPreResReq=2).uDam is greater than
95%, send 1 request (yZonPreResReq=1) until
uDam is less than 85%.uDam is less than 95%,
send 0 request (yZonPreResReq=0).