.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctColdDuctMin.Subsequences.ActiveAirFlow

Information

This sequence sets the active cooling and heating maximum and the active minimum setpoints for dual-duct terminal unit with cold-duct minimum control. The implementation is according to the Section 5.14.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint OccupiedCooldown SetupWarm-upSetbackUnoccupied
Cooling maximum (VActCooMax_flow)VCooMax_flow VCooMax_flowVCooMax_flow 000
Minimum (VActMin_flow)VOccMin_flow0 0000
Heating maximum (VActHeaMax_flow)VHeaMax_flow 00VHeaMax_flowVHeaMax_flow 0

Note that the designer must ensure that the minimum (VOccMin_flow) and heating maximum (VHeaMax_flow) sum to less than the cooling maximum (VCooMax_flow) to avoid oversupplying the diffusers.