This block outputs alarms of dual-duct terminal unit with cold-duct minimum control. The implementation is according to the Section 5.14.6 of ASHRAE Guideline 36, May 2020. Note that the sequence uses two airflow sensors, one at each inlet.
staTim,
if the measured airflow (VColDucDis_flow plus VHotDucDis_flow) is less than 70% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 3 alarm.
staTim,
if the measured airflow (VColDucDis_flow plus VHotDucDis_flow) is less than 50% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 2 alarm.
staPreMul) of 0 for its
static pressure reset Trim-Respond control loop, low airflow alarms shall be
suppressed for that zone.
u1CooFan=false) for 10 minutes
(fanOffTim), and the cold-duct airflow sensor reading VColDucDis_flow
is above 10% of the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
u1HeaFan=false) for 10 minutes
(fanOffTim), and the hot-duct airflow sensor reading VHotDucDis_flow
is above 10% of the heating maximum airflow setpoint VHeaMax_flow,
generate a Level 3 alarm.
uCooDam) is 0% and airflow sensor reading
VColDucDis_flow is above 10% of the cooling maximum airflow setpoint
VCooMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1CooFan=true), generate a Level
4 alarm.
uHeaDam) is 0% and airflow sensor reading
VHotDucDis_flow is above 10% of the heating maximum airflow setpoint
VHeaMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1HeaFan=true), generate a Level
4 alarm.
Logical.And3 based on ASHRAE 231P,
replaced it with a stack of two Logical.And blocks.
This is for
#2465.
staTim to allow the system becoming stabilized.
This is for issue 3257.