This block outputs alarms of dual-duct terminal unit with cold-duct minimum control. The implementation is according to the Section 5.14.6 of ASHRAE Guideline 36, May 2020. Note that the sequence uses two airflow sensors, one at each inlet.
staTim, if the measured airflow
(VColDucDis_flow plus VHotDucDis_flow) is
less than 70% of setpoint VActSet_flow for 5 minutes
(lowFloTim) while the setpoint is greater than zero,
generate a Level 3 alarm.staTim, if the measured airflow
(VColDucDis_flow plus VHotDucDis_flow) is
less than 50% of setpoint VActSet_flow for 5 minutes
(lowFloTim) while the setpoint is greater than zero,
generate a Level 2 alarm.staPreMul)
of 0 for its static pressure reset Trim-Respond control loop, low
airflow alarms shall be suppressed for that zone.u1CooFan=false) for 10 minutes
(fanOffTim), and the cold-duct airflow sensor reading
VColDucDis_flow is above 10% of the cooling maximum
airflow setpoint VCooMax_flow, generate a Level 3
alarm.u1HeaFan=false) for 10 minutes
(fanOffTim), and the hot-duct airflow sensor reading
VHotDucDis_flow is above 10% of the heating maximum
airflow setpoint VHeaMax_flow, generate a Level 3
alarm.uCooDam) is 0% and
airflow sensor reading VColDucDis_flow is above 10% of
the cooling maximum airflow setpoint VCooMax_flow for
10 minutes (leaFloTim) while the fan serving the zone
is proven on (u1CooFan=true), generate a Level 4
alarm.uHeaDam) is 0% and
airflow sensor reading VHotDucDis_flow is above 10% of
the heating maximum airflow setpoint VHeaMax_flow for
10 minutes (leaFloTim) while the fan serving the zone
is proven on (u1HeaFan=true), generate a Level 4
alarm.Logical.And3 based on ASHRAE
231P, replaced it with a stack of two Logical.And
blocks. This is for #2465.staTim to allow the system becoming
stabilized. This is for issue
3257.