This sequence outputs the system reset requests for dual-duct terminal unit with cold-duct minimum control. The implementation is according to the Section 5.14.8 of ASHRAE Guideline 36, May 2020.
yZonCooTemResReqTZon exceeds the zone cooling setpoint
TCooSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupCoo=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonCooTemResReq=3).
TZon exceeds the zone cooling setpoint
TCooSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupCoo=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonCooTemResReq=3).
uCoo is greater than 95%, send 1 request
(yZonCooTemResReq=1) until uCoo is less than 85%.
uCoo is less than 95%, send 0 request (yZonCooTemResReq=0).
yColDucPreResReqVColDucDis_flow is less than 50% of setpoint
VColDuc_flow_Set while the setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 3 requests (yColDucPreResReq=3).
VColDucDis_flow is less than 70% of setpoint
VColDuc_flow_Set while the setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 2 requests (yColDucPreResReq=2).
uCooDam is greater than 95%, send 1 request
(yColDucPreResReq=1) until uDam is less than 85%.
uCooDam is less than 95%, send 0 request
(yColDucPreResReq=0).
yZonHeaTemResReqTZon is below the zone heating setpoint
THeaSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupHea=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonHeaTemResReq=3).
TZon is below the zone heating setpoint
THeaSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupHea=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonHeaTemResReq=3).
uHea is greater than 95%, send 1 request
(yZonHeaTemResReq=1) until uHea is less than 85%.
uHea is less than 95%, send 0 request (yZonHeaTemResReq=0).
yHotDucPreResReqVHotDucDis_flow is less than 50% of setpoint
VHotDuc_flow_Set while the setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 3 requests (yHotDucPreResReq=3).
VHotDucDis_flow is less than 70% of setpoint
VHotDuc_flow_Set while the setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 2 requests (yHotDucPreResReq=2).
uHeaDam is greater than 95%, send 1 request
(yHotDucPreResReq=1) until uHeaDam is less than 85%.
uHeaDam is less than 95%, send 0 request
(yHotDucPreResReq=0).
Send the heating fan that serves the zone a heating-fan request as follows: