This block outputs alarms of dual-duct terminal unit using mixing control with discharge flow sensor. The implementation is according to the Section 5.13.6 of ASHRAE Guideline 36, May 2020.
staTim,
if the measured airflow VDis_flow is less than 70% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 3 alarm.
staTim,
if the measured airflow VDis_flow is less than 50% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 2 alarm.
staPreMul) of 0 for its
static pressure reset Trim-Respond control loop, low airflow alarms shall be
suppressed for that zone.
u1CooFan=false
and u1HeaFan=false) for 10 minutes (fanOffTim), and the
discharge airflow sensor reading VDis_flow
is above 10% of the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
uCooDam and uHeaDam)
are 0% and airflow sensor reading
VDis_flow is above 10% of the cooling maximum airflow setpoint
VCooMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1CooFan=true or u1HeaFan=true),
generate a Level 4 alarm.
Logical.And3 based on ASHRAE 231P,
replaced it with a stack of two Logical.And blocks.
This is for
#2465.
staTim to allow the system becoming stabilized.
This is for issue 3257.