This block outputs alarms of dual-duct terminal unit using mixing control with discharge flow sensor. The implementation is according to the Section 5.13.6 of ASHRAE Guideline 36, May 2020.
staTim, if the measured airflow
VDis_flow is less than 70% of setpoint
VActSet_flow for 5 minutes (lowFloTim)
while the setpoint is greater than zero, generate a Level 3
alarm.staTim, if the measured airflow
VDis_flow is less than 50% of setpoint
VActSet_flow for 5 minutes (lowFloTim)
while the setpoint is greater than zero, generate a Level 2
alarm.staPreMul)
of 0 for its static pressure reset Trim-Respond control loop, low
airflow alarms shall be suppressed for that zone.u1CooFan=false and u1HeaFan=false) for
10 minutes (fanOffTim), and the discharge airflow
sensor reading VDis_flow is above 10% of the cooling
maximum airflow setpoint VCooMax_flow, generate a
Level 3 alarm.uCooDam and uHeaDam) are 0% and airflow
sensor reading VDis_flow is above 10% of the cooling
maximum airflow setpoint VCooMax_flow for 10 minutes
(leaFloTim) while the fan serving the zone is proven
on (u1CooFan=true or u1HeaFan=true),
generate a Level 4 alarm.Logical.And3 based on ASHRAE
231P, replaced it with a stack of two Logical.And
blocks. This is for #2465.staTim to allow the system becoming
stabilized. This is for issue
3257.