This block considers the overrides to the setpoints for dual-duct terminal unit using mixing control with discharge flow sensor. The implementation is according to the Section 5.13.7 of ASHRAE Guideline 36, May 2020.
Provide software switches that interlock to a system-level point to:
oveFloSet
equals to 1, force the zone airflow setpoint
VSet_flow
to zero,
oveFloSet
equals to 2, force the zone airflow setpoint
VSet_flow
to zone cooling maximum airflow rate
VCooMax_flow
,
oveFloSet
equals to 3, force the zone airflow setpoint
VSet_flow
to zone minimum airflow setpoint
VMin_flow
.
oveFloSet
equals to 4, force the zone airflow setpoint
VSet_flow
to zone heating maximum airflow setpoint
VHeaMax_flow
.
oveCooDamPos
equals to 1, force the cooling damper to full closed by setting
yCooDam
to 0,
oveCooDamPos
equals to 2, force the cooling damper to full open by setting
yCooDam
to 1.
oveHeaDamPos
equals to 1, force the heating damper to full closed by setting
yHeaDam
to 0,
oveHeaDamPos
equals to 2, force the heating damper to full open by setting
yHeaDam
to 1.