This sequence outputs the system reset requests for dual-duct terminal unit using mixing control with discharge flow sensor. The implementation is according to the Section 5.13.8 of ASHRAE Guideline 36, May 2020.
yZonCooTemResReqTZon exceeds the zone cooling setpoint
TCooSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupCoo=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonCooTemResReq=3).
TZon exceeds the zone cooling setpoint
TCooSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupCoo=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonCooTemResReq=3).
uCoo is greater than 95%, send 1 request
(yZonCooTemResReq=1) until uCoo is less than 85%.
uCoo is less than 95%, send 0 request (yZonCooTemResReq=0).
yColDucPreResReqWhen the zone is in cooling or deadband state:
VDis_flow is less than 50% of setpoint
VDis_flow_Set while the setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 3 requests (yColDucPreResReq=3).
VDis_flow is less than 70% of setpoint
VDis_flow_Set while the setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 2 requests (yColDucPreResReq=2).
uCooDam is greater than 95%, send 1 request
(yColDucPreResReq=1) until uDam is less than 85%.
uCooDam is less than 95%, send 0 request
(yColDucPreResReq=0).
yZonHeaTemResReqTZon is below the zone heating setpoint
THeaSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupHea=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonHeaTemResReq=3).
TZon is below the zone heating setpoint
THeaSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupHea=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonHeaTemResReq=3).
uHea is greater than 95%, send 1 request
(yZonHeaTemResReq=1) until uHea is less than 85%.
uHea is less than 95%, send 0 request (yZonHeaTemResReq=0).
yHotDucPreResReqWhen the zone is in heating state:
VDis_flow is less than 50% of setpoint
VDis_flow_Set while the setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 3 requests (yHotDucPreResReq=3).
VDis_flow is less than 70% of setpoint
VDis_flow_Set while the setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 2 requests (yHotDucPreResReq=2).
uHeaDam is greater than 95%, send 1 request
(yHotDucPreResReq=1) until uHeaDam is less than 85%.
uHeaDam is less than 95%, send 0 request
(yHotDucPreResReq=0).
Send the heating fan that serves the zone a heating-fan request as follows: