This block outputs alarms of dual-duct terminal unit using mixing control with inlet sensor. The implementation is according to the Section 5.12.6 of ASHRAE Guideline 36, May 2020. Note that the sequence uses two airflow sensors, one at each inlet.
staTim
,
if the measured airflow VDis_flow
is less than 70% of setpoint
VActSet_flow
for 5 minutes (lowFloTim
) while the setpoint
is greater than zero, generate a Level 3 alarm.
staTim
,
if the measured airflow VDis_flow
is less than 50% of setpoint
VActSet_flow
for 5 minutes (lowFloTim
) while the setpoint
is greater than zero, generate a Level 2 alarm.
staPreMul
) of 0 for its
static pressure reset Trim-Respond control loop, low airflow alarms shall be
suppressed for that zone.
u1CooFan=false
) for 10 minutes
(fanOffTim
), and the cold-duct airflow sensor reading VColDucDis_flow
is above 10% of the cooling maximum airflow setpoint VCooMax_flow
,
generate a Level 3 alarm.
u1HeaFan=false
) for 10 minutes
(fanOffTim
), and the hot-duct airflow sensor reading VHotDucDis_flow
is above 10% of the heating maximum airflow setpoint VHeaMax_flow
,
generate a Level 3 alarm.
uCooDam
) is 0% and airflow sensor reading
VColDucDis_flow
is above 10% of the cooling maximum airflow setpoint
VCooMax_flow
for 10 minutes (leaFloTim
) while the
fan serving the zone is proven on (u1CooFan=true
), generate a Level
4 alarm.
uHeaDam
) is 0% and airflow sensor reading
VHotDucDis_flow
is above 10% of the heating maximum airflow setpoint
VHeaMax_flow
for 10 minutes (leaFloTim
) while the
fan serving the zone is proven on (u1HeaFan=true
), generate a Level
4 alarm.
Logical.And3
based on ASHRAE 231P,
replaced it with a stack of two Logical.And
blocks.
This is for
#2465.
staTim
to allow the system becoming stabilized.
This is for issue 3257.