This sequence sets the dampers for dual-duct terminal unit using mixing control with inlet flow sensor. The implementation is according to Section 5.12.5 of ASHRAE Guideline 36, May 2020. The calculation is done following the steps below.
uCoo > 0
), then the cooling loop output
uCoo
shall reset the cooling supply airflow setpoint
VColDucDis_flow_Set
from the minimum VActMin_flow
to
cooling maximum setpoint VActCooMax_flow
. The cooling damper shall be
modulated by a control loop to maintain the measured cooling aiflow
VColDucDis_flow
at setpoint. The heating damper shall be closed
yHeaDam=0
.
TColSup
from the cooling air handler
is greater than room temperature TZon
, cooling supply airflow setpoint shall be
no higher than the minimum.
uCoo=0
and uHea=0
), the cooling
airflow set point VColDucDis_flow_Set
shall be the minimum set point
VActMin_flow
. The cooling damper shall be modulated by a control loop
to maintain the measured cooling airflow at set point. The heating damper shall be closed.
uHea > 0
), then the heating loop output
uHea
shall reset the heating supply airflow setpoint
VHotDucDis_flow_Set
from zero to
heating maximum setpoint VActHeaMax_flow
. The heating damper shall be
modulated by a control loop to maintain the measured heating aiflow
VHotDucDis_flow
at setpoint.
The cooling damper shall be controlled to maintain the sum of the measured inlet
airflows at the minimum airflow set point VActMin_flow
.
THotSup
from the heating air handler
is less than room temperature TZon
, heating supply airflow setpoint shall be
no higher than the minimum.
u1HeaAHU=false
), the heating
damper shall be closed (yHeaDam=0
).
u1CooAHU=false
), the cooling
damper shall be closed (yCooDam=0
).
The sequences of controlling dampers position for dual-duct terminal unit using mixing control with inlet flow sensor are described in the following figure below.
have_preIndDam
to exclude the option of using pressure independant damper.