This sequence outputs the system reset requests for dual-duct terminal unit using mixing control with inlet flow sensor. The implementation is according to the Section 5.12.8 of ASHRAE Guideline 36, May 2020.
yZonCooTemResReq
TZon
exceeds the zone cooling setpoint
TCooSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupCoo=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonCooTemResReq=3
).
TZon
exceeds the zone cooling setpoint
TCooSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupCoo=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonCooTemResReq=3
).
uCoo
is greater than 95%, send 1 request
(yZonCooTemResReq=1
) until uCoo
is less than 85%.
uCoo
is less than 95%, send 0 request (yZonCooTemResReq=0
).
yColDucPreResReq
VColDucDis_flow
is less than 50% of setpoint
VColDuc_flow_Set
while the setpoint is greater than zero and the damper position
uCooDam
is greater than 95% for 1 minute, send 3 requests (yColDucPreResReq=3
).
VColDucDis_flow
is less than 70% of setpoint
VColDuc_flow_Set
while the setpoint is greater than zero and the damper position
uCooDam
is greater than 95% for 1 minute, send 2 requests (yColDucPreResReq=2
).
uCooDam
is greater than 95%, send 1 request
(yColDucPreResReq=1
) until uDam
is less than 85%.
uCooDam
is less than 95%, send 0 request
(yColDucPreResReq=0
).
yZonHeaTemResReq
TZon
is below the zone heating setpoint
THeaSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupHea=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonHeaTemResReq=3
).
TZon
is below the zone heating setpoint
THeaSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupHea=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonHeaTemResReq=3
).
uHea
is greater than 95%, send 1 request
(yZonHeaTemResReq=1
) until uHea
is less than 85%.
uHea
is less than 95%, send 0 request (yZonHeaTemResReq=0
).
yHotDucPreResReq
VHotDucDis_flow
is less than 50% of setpoint
VHotDuc_flow_Set
while the setpoint is greater than zero and the damper position
uHeaDam
is greater than 95% for 1 minute, send 3 requests (yHotDucPreResReq=3
).
VHotDucDis_flow
is less than 70% of setpoint
VHotDuc_flow_Set
while the setpoint is greater than zero and the damper position
uHeaDam
is greater than 95% for 1 minute, send 2 requests (yHotDucPreResReq=2
).
uHeaDam
is greater than 95%, send 1 request
(yHotDucPreResReq=1
) until uHeaDam
is less than 85%.
uHeaDam
is less than 95%, send 0 request
(yHotDucPreResReq=0
).
Send the heating fan that serves the zone a heating-fan request as follows: