This sequence outputs the system reset requests for dual-duct terminal unit using mixing control with inlet flow sensor. The implementation is according to the Section 5.12.8 of ASHRAE Guideline 36, May 2020.
yZonCooTemResReqTZon exceeds the zone
cooling setpoint TCooSet by 3 °C (5 °F)) for 2 minutes
and after suppression period (uAftSupCoo=true) due to
setpoint change per G36 Part 5.1.20, send 3 requests
(yZonCooTemResReq=3).TZon exceeds the zone
cooling setpoint TCooSet by 2 °C (3 °F) for 2 minutes
and after suppression period (uAftSupCoo=true) due to
setpoint change per G36 Part 5.1.20, send 2 requests
(yZonCooTemResReq=3).uCoo is greater than 95%,
send 1 request (yZonCooTemResReq=1) until
uCoo is less than 85%.uCoo is less than 95%, send 0 request
(yZonCooTemResReq=0).yColDucPreResReqVColDucDis_flow is less
than 50% of setpoint VColDuc_flow_Set while the
setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 3
requests (yColDucPreResReq=3).VColDucDis_flow is
less than 70% of setpoint VColDuc_flow_Set while the
setpoint is greater than zero and the damper position
uCooDam is greater than 95% for 1 minute, send 2
requests (yColDucPreResReq=2).uCooDam is greater
than 95%, send 1 request (yColDucPreResReq=1) until
uDam is less than 85%.uCooDam is less than
95%, send 0 request (yColDucPreResReq=0).yZonHeaTemResReqTZon is below the zone
heating setpoint THeaSet by 3 °C (5 °F)) for 2 minutes
and after suppression period (uAftSupHea=true) due to
setpoint change per G36 Part 5.1.20, send 3 requests
(yZonHeaTemResReq=3).TZon is below the
zone heating setpoint THeaSet by 2 °C (3 °F) for 2
minutes and after suppression period (uAftSupHea=true)
due to setpoint change per G36 Part 5.1.20, send 2 requests
(yZonHeaTemResReq=3).uHea is greater than 95%,
send 1 request (yZonHeaTemResReq=1) until
uHea is less than 85%.uHea is less than 95%, send 0 request
(yZonHeaTemResReq=0).yHotDucPreResReqVHotDucDis_flow is less
than 50% of setpoint VHotDuc_flow_Set while the
setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 3
requests (yHotDucPreResReq=3).VHotDucDis_flow is
less than 70% of setpoint VHotDuc_flow_Set while the
setpoint is greater than zero and the damper position
uHeaDam is greater than 95% for 1 minute, send 2
requests (yHotDucPreResReq=2).uHeaDam is greater
than 95%, send 1 request (yHotDucPreResReq=1) until
uHeaDam is less than 85%.uHeaDam is less than
95%, send 0 request (yHotDucPreResReq=0).Send the heating fan that serves the zone a heating-fan request as follows: