.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.ActiveAirFlow

Output the active airflow setpoint for snap-acting controlled dual-duct terminal unit

Information

This sequence sets the active cooling and heating maximum and the active minimum setpoints for snap-acting controlled dual-duct terminal unit. The implementation is according to the Section 5.11.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint Occupied Cooldown Setup Warm-up Setback Unoccupied
Cooling maximum (VActCooMax_flow) VCooMax_flow VCooMax_flow VCooMax_flow 0 0 0
Minimum (VActMin_flow) VOccMin_flow 0 0 0 0 0
Heating maximum (VActHeaMax_flow) VHeaMax_flow 0 0 VHeaMax_flow VHeaMax_flow 0