.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.Alarms

Information

This block outputs alarms of snap-acting controlled dual-duct terminal unit. The implementation is according to the Section 5.11.6 of ASHRAE Guideline 36, May 2020.

Low airflow

  1. If the zone is in occupied mode and after the AHU supply fan has been enabled for staTim, if the measured airflow VDis_flow is less than 70% of setpoint VActSet_flow for 5 minutes (lowFloTim) while the setpoint is greater than zero, generate a Level 3 alarm.
  2. If the zone is in occupied mode and after the AHU supply fan has been enabled for staTim, if the measured airflow VDis_flow is less than 50% of setpoint VActSet_flow for 5 minutes (lowFloTim) while the setpoint is greater than zero, generate a Level 2 alarm.
  3. If a zone has an importance multiplier (staPreMul) of 0 for its static pressure reset Trim-Respond control loop, low airflow alarms shall be suppressed for that zone.

Airflow sensor calibration

Leaking damper

Revisions


Generated at 2024-11-23T19:25:52Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos