This block outputs alarms of snap-acting controlled dual-duct terminal unit. The implementation is according to the Section 5.11.6 of ASHRAE Guideline 36, May 2020.
staTim,
if the measured airflow VDis_flow is less than 70% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 3 alarm.
staTim,
if the measured airflow VDis_flow is less than 50% of setpoint
VActSet_flow for 5 minutes (lowFloTim) while the setpoint
is greater than zero, generate a Level 2 alarm.
staPreMul) of 0 for its
static pressure reset Trim-Respond control loop, low airflow alarms shall be
suppressed for that zone.
have_duaSen=true):
u1CooFan=false) for 10 minutes
(fanOffTim), and the cold-duct airflow sensor reading VColDucDis_flow
is above 10% of the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
u1HeaFan=false) for 10 minutes
(fanOffTim), and the hot-duct airflow sensor reading VHotDucDis_flow
is above 10% of the heating maximum airflow setpoint VHeaMax_flow,
generate a Level 3 alarm.
have_duaSen=false):
u1CooFan=false
and u1HeaFan=false) for 10 minutes (fanOffTim), and the
discharge airflow sensor reading VDis_flow
is above 10% of the cooling maximum airflow setpoint VCooMax_flow,
generate a Level 3 alarm.
have_duaSen=true):
uCooDam) is 0% and airflow sensor reading
VColDucDis_flow is above 10% of the cooling maximum airflow setpoint
VCooMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1CooFan=true), generate a Level
4 alarm.
uHeaDam) is 0% and airflow sensor reading
VHotDucDis_flow is above 10% of the heating maximum airflow setpoint
VHeaMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1HeaFan=true), generate a Level
4 alarm.
have_duaSen=false):
uCooDam and uHeaDam)
are 0% and airflow sensor reading
VDis_flow is above 10% of the cooling maximum airflow setpoint
VCooMax_flow for 10 minutes (leaFloTim) while the
fan serving the zone is proven on (u1CooFan=true or u1HeaFan=true),
generate a Level 4 alarm.
Logical.And3 based on ASHRAE 231P,
replaced it with a stack of two Logical.And blocks.
This is for
#2465.
staTim to allow the system becoming stabilized.
This is for issue 3257.