This sequence outputs the system reset requests for snap-acting controlled dual-duct terminal unit. The implementation is according to the Section 5.11.8 of ASHRAE Guideline 36, May 2020.
yZonCooTemResReq
TZon
exceeds the zone cooling setpoint
TCooSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupCoo=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonCooTemResReq=3
).
TZon
exceeds the zone cooling setpoint
TCooSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupCoo=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonCooTemResReq=3
).
uCoo
is greater than 95%, send 1 request
(yZonCooTemResReq=1
) until uCoo
is less than 85%.
uCoo
is less than 95%, send 0 request (yZonCooTemResReq=0
).
yColDucPreResReq
VColDucDis_flow
is less than 50% of setpoint
VColDuc_flow_Set
while the setpoint is greater than zero and the damper position
uCooDam
is greater than 95% for 1 minute, send 3 requests (yColDucPreResReq=3
).
VColDucDis_flow
is less than 70% of setpoint
VColDuc_flow_Set
while the setpoint is greater than zero and the damper position
uCooDam
is greater than 95% for 1 minute, send 2 requests (yColDucPreResReq=2
).
uCooDam
is greater than 95%, send 1 request
(yColDucPreResReq=1
) until uDam
is less than 85%.
uCooDam
is less than 95%, send 0 request
(yColDucPreResReq=0
).
yZonHeaTemResReq
TZon
is below the zone heating setpoint
THeaSet
by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSupHea=true
) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonHeaTemResReq=3
).
TZon
is below the zone heating setpoint
THeaSet
by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSupHea=true
) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonHeaTemResReq=3
).
uHea
is greater than 95%, send 1 request
(yZonHeaTemResReq=1
) until uHea
is less than 85%.
uHea
is less than 95%, send 0 request (yZonHeaTemResReq=0
).
yHotDucPreResReq
VHotDucDis_flow
is less than 50% of setpoint
VHotDuc_flow_Set
while the setpoint is greater than zero and the damper position
uHeaDam
is greater than 95% for 1 minute, send 3 requests (yHotDucPreResReq=3
).
VHotDucDis_flow
is less than 70% of setpoint
VHotDuc_flow_Set
while the setpoint is greater than zero and the damper position
uHeaDam
is greater than 95% for 1 minute, send 2 requests (yHotDucPreResReq=2
).
uHeaDam
is greater than 95%, send 1 request
(yHotDucPreResReq=1
) until uHeaDam
is less than 85%.
uHeaDam
is less than 95%, send 0 request
(yHotDucPreResReq=0
).
Send the heating fan that serves the zone a heating-fan request as follows: