.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.Reheat.Subsequences.ActiveAirFlow

Output the active airflow setpoint for VAV reheat terminal unit

Information

This sequence sets the active cooling and heating maximum and minimum setpoints for VAV reheat terminal unit. The implementation is according to the Section 5.6.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint Occupied Cooldown Setup Warm-up Setback Unoccupied
Cooling maximum (VActCooMax_flow) VCooMax_flow VCooMax_flow VCooMax_flow 0 0 0
Cooling minimum (VActCooMin_flow) VOccMin_flow 0 0 0 0 0
Minimum (VActMin_flow) VOccMin_flow 0 0 0 0 0
Heating minimum (VActHeaMin_flow) max(VHeaMin_flow,VOccMin_flow) VHeaMin_flow 0 VHeaMax_flow VHeaMax_flow 0
Heating maximum (VActHeaMax_flow) max(VHeaMax_flow,VOccMin_flow) VHeaMax_flow 0 VCooMax_flow VCooMax_flow 0

Revisions


Generated at 2026-04-14T18:18:34Z by OpenModelicaOpenModelica 1.26.3 using GenerateDoc.mos