This sequence outputs the system reset requests for terminal unit with reheat. The implementation is according to the Section 5.6.8 of ASHRAE Guideline 36, May 2020.
yZonTemResReqTZon exceeds the zone cooling setpoint
TCooSet by 3 °C (5 °F)) for 2 minutes and after suppression
period (uAftSup=true) due to setpoint change per G36 Part 5.1.20,
send 3 requests (yZonTemResReq=3).
TZon exceeds the zone cooling setpoint
TCooSet by 2 °C (3 °F) for 2 minutes and after suppression
period (uAftSup=true) due to setpoint change per G36 Part 5.1.20,
send 2 requests (yZonTemResReq=2).
uCoo is greater than 95%, send 1 request
(yZonTemResReq=1) until uCoo is less than 85%.
uCoo is less than 95%, send 0 request (yZonTemResReq=0).
yZonPreResReqVDis_flow is less than 50% of setpoint
VSet_flow while the setpoint is greater than zero and the damper position
uDam is greater than 95% for 1 minute, send 3 requests (yZonPreResReq=3).
VDis_flow is less than 70% of setpoint
VSet_flow while the setpoint is greater than zero and the damper position
uDam is greater than 95% for 1 minute, send 2 requests (yZonPreResReq=2).
uDam is greater than 95%, send 1 request
(yZonPreResReq=1) until uDam is less than 85%.
uDam is less than 95%, send 0 request
(yZonPreResReq=0).
yHeaValResReqTDis is 17 °C (30 °F)
thrTDis_1 less than the setpoint TDisSet
for 5 minutes, send 3 requests.
TDis is 8 °C (15 °F)
thrTDis_1 less than the setpoint TDisSet
for 5 minutes, send 2 requests.
uVal is greater than 95%, send 1
request until the hot water valve position is less than 85%.
uVal is less than 95%, send 0 request.
uVal is greater than 95%, send 1
request until the hot water valve position is less than 10%.
uVal is less than 95%, send 0 requests.