.Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.SeriesFanCVF.Subsequences.ActiveAirFlow

Information

This sequence sets the active primary cooling maximum and minimum setpoints for series fan-powered terminal unit with constant volume fan. The implementation is according to the Section 5.9.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint OccupiedCooldown SetupWarm-upSetbackUnoccupied
Cooling maximum (VActCooMax_flow)VCooMax_flow VCooMax_flowVCooMax_flow 000
Minimum (VActMin_flow)VOccMin_flow0 0000

Revisions